5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
111
5
Element Optional function
Individual
setting
Settings
Setting conditions Description
Cd
Stop of indoor unit fan
during cooling
Thermo-OFF conditions
? NOTE
For model
RPI-FSN3E(P)E and
RCD-FSR, this function
is NOT available.
O
00
Fan speed during cooling Thermo-
OFF: Low (factory setting)
The operation of the indoor
unit fan is stopped in cooling
Thermo-OFF conditions when
using the additional remote
temperature sensor THM-R2AE
(connected to THM4) or the PC-
ARFP1E temperature sensor.
C8 must be set to 01 to use the
Cd=01 setting.
01
Indoor unit fan is stopped during
cooling Thermo-OFF
CE
Stop of indoor unit fan
during heating
Thermo-OFF conditions
Stop of indoor unit fan
during heating
Thermo-OFF conditions
(with remote control
switch temperature
sensor)
O
00
Fan speed setting during heating
Thermo-OFF: Low (factory setting)
The indoor unit uses the
PC-ARFP1E temperature
sensor to monitor the room
temperature when the fan is
stopped (heating Thermo-OFF
fan stop sequence).
C8 must be set to 01 to use the
CE=01 setting.
Control by remote temperature
sensor connected to THM4 is
not permitted (use E8 function in
that case).
01
Indoor unit fan is stopped during
heating Thermo-OFF.
(In case that automatic louvre is set,
the louvres will keep operating in
both Thermo-ON and Thermo-OFF
conditions)
CF
Modication of louvre 
swing range
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
O
00
Standard (7 steps)
(factory setting)
This function adjusts the angle
of the air outlet louvre.
(Changes to the setting of this
function are applied after turning
the power supply o and on
again, or after the automatic
louvre has made a full cycle in
automatic mode)
01
Cold draft prevention (5 steps)
(Cannot be set to the lower two steps;
lower 2 steps cut o)
02
High ceilings (5 steps)
(Cannot be set the upper two steps;
upper 2 steps cut o)
Models:
RPK-FSR(H)M
00
Standard (7 steps)
(5 steps for cooling / dry mode)
01
Cold draft prevention
(5 steps for heating and fan only)
(Cannot be set to the lower two steps,
lower 2 steps cut o)
02
Not used
d1
Management of indoor
unit operation after a
power supply cut o󰀨 - 
option 1
O
00
Function disabled
(factory setting)
When power supply is restored,
the indoor units controlled by
the wired remote control switch
are turned on regardless of their
ON/OFF status at the time of the
last power cut o󰀨. 
01
Function enabled
d2
Not available
“- -”
permanent
d3
Management of indoor
unit operation after a
power supply cut o󰀨 - 
option 2
O
00
Function disabled
(factory setting)
When power supply is restored,
the indoor units controlled by the
wired remote control switch are
turned on automatically ONLY
if they were already ON at the
time of the last power cut o󰀨. 
If indoor units were OFF when
power was turned OFF, they
remain in OFF status when
power is restored.
01
Function enabled