5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
148
Item Optional function
Individual
Setting
Settings Setting conditions Description
EC
Forced Thermo-ON
when stopping in
cooling operation
00
Function disabled
(factory setting)
This function is used to force
Thermo-ON during 6 minutes when
stopping in cooling operation.
01 Enabled
Ed
Not used -
00
- Use at 00 conditions
01
EE
Control in
“Automatic” indoor
fan speed mode
00
Function disabled
(factory setting)
This function limits the speed of the
indoor fan when room temperature is
close to the setting temperature.
01 Enabled
EF
Control in
“Automatic” indoor
fan speed mode
(supporting High H)
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
00 Function disabled
This function limits the speed of the
indoor fan when room temperature
is close to the setting temperature,
allowing to reach High H speed.
01 Function enabled
F0
Not available -
“- -”
permanent
F1
Automatic OFF
timer setting
Models:
RCI-FSR
RPC-FSR
RPK-FSRM
RPI(L/H)-FSRE
RCD-FSR
RCIM-FSRE
RPI-FSN3(P)E
×
00
Function disabled
(Factory setting)
This function sets an automatic OFF
timer to switch OFF the indoor units
controlled by the remote control
switch (when the units have been
started by remote control).
(Do not set the values "0C"-"0F"
when two remote control switches
are used in the same remote control
group)
01 1 hour
02 2 hours
03 3 hours
04-24 (04-24) hours
0A 30 minutes
0B 90 minutes
0C 40 minutes
}
Do not set these
when two wired
controllers are
used.
0D 45 minutes
0E 50 minutes
0F 55 minutes
Automatic OFF
timer setting
Models:
RPF(I)-FSN2E
×
00
Function disabled
(Factory setting)
This function is used to set the
automatic timer to switch o󰀨 when 
the unit has been started by remote
control.
01 1 hour
02 2 hours
03 3 hours
04-24 (04-24) hours
0A 30 minutes
0B 90 minutes
F2
Remote control
main-sub setting
×
00
Main (Master remote control)
(Factory setting)
This function is used to dene which 
remote control switch is used as
master or slave, when two remote
controllers are connected to one
indoor unit.
01 Sub (Slave remote control)