5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
149
5
Item Optional function
Individual
Setting
Settings Setting conditions Description
F3
Automatic reset of
setting temperature
×
00
Function disabled
(Factory setting)
This function is used to limit unit
operation and save energy.
The setting temperature is
automatically set to the value
dened with functions "F5" or "F6", 
according to the current operation
mode, after the time set with
function "F4" has passed since 
the last manual change of setting
temperature.
In case that the values of "F5" or 
"F6" are out of the limits set with 
functions "FC" and "Fd", limitations 
set by "FC" and "Fd" have priority.
01 Function enabled
F4
Automatic reset time ×
00 30 minutes (factory setting)
This function sets the automatic
reset time delay for function F3.
01 15 minutes
02 60 minutes
03 90 minutes
F5
Automatic reset
temperature for
cooling
×
19 19 °C
This function denes the default 
temperature set point for the
automatic reset function F3 in FAN/
COOL/DRY modes.
20 20 °C
21 21 °C
·
·
·
·
·
·
24 24 °C
25 25 °C (factory setting)
26 26 ºC
·
·
·
·
·
·
28 28 ºC
29 29 ºC
30 30 ºC
F6
Automatic reset
temperature for
heating
×
17 17 ºC
This function denes the default 
temperature set point for the
automatic reset function F3 in HEAT
mode.
18 18 ºC
·
·
·
·
·
·
20 20 ºC
21 21 ºC (factory setting)
25 25 ºC
·
·
·
·
·
·
28 28 ºC
29 29 ºC
30 30 ºC
F7
Prevention of
operation stoppage
due to wrong
operation of the
remote controller
×
00
Function disabled
(factory setting)
Operation is stopped by pressing the
run/stop switch for 3 seconds.
01 Function enabled
F8
Lock function for
operation mode
selection
×
00 Function disabled
This function is used to prevent
changes to the operation mode.
01
Function enabled
(factory setting)
Fg
Lock function for
temperature setting
×
00 Function disabled
This function is used to prevent
changes to the temperature setting.
01
Function enabled
(factory setting)