5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
153
5
Item Optional function
Individual
Setting
Settings Setting conditions Description
L3
Operation of the
louvres in energy-
saving Thermo-OFF
(Cooling / Dry mode)
00 Direct air blow Low (factory setting)
Power save must be ON in order to
use this function (L5 must be set to
01).
This function is used to establish
louvre swinging operation ranging
from continuous swing to static
operation.
Low: Continuous louvre swing
Medium: Louvre swing with
intermittent stops for 20/40 seconds
High: Louvre stopped at full opening
position, according to the setting of
CF.
01 Direct air blow Medium
02 Direct air blow High
03 Disabled
L4
Fan acceleration
in energy-saving
Thermo-OFF
(Cooling mode)
00
Function disabled
(factory setting)
This function increases fan speed
by one step to prevent the loss of
comfort due to the forced Thermo-
OFF for energy saving during
cooling operation.
01 Function enabled
L5
Louvre swing
operation during
energy-saving
forced Thermo-OFF
00
Function disabled
(factory setting)
This function is used to enabled the
setting of function L3.
01 Function enabled
L6
Not used -
00
- Use at 00 conditions
01
L7
Not available -
“- -”
permanent
L8
Not used -
00
- Use at 00 conditions
01
Lg
Not used
00
- Use at 00 conditions
01
LA
Not used -
00
- Use at 00 conditions
01
Lb
Not used -
00
- Use at 00 conditions
01
P1
Setting temperature
in 0.5 ºC steps
×
00
Enabled (0.5 °C steps)
(factory setting)
This function is used to dene 
whether setting temperature is
adjusted in 0.5 ºC steps (when set
to “00”) or in 1 ºC steps (when set
to “01”).
This setting also determines whether
the resolution of temperature
di󰀨erential of the thermistor is 0.5 ºC 
(when set to “00”) or 1 ºC (when set
to “01”).
01 Disabled (1 °C steps)
P2
Not used -
00
- Use at 00 conditions
01
P3
Temperature sensor
displayed
×
00 Inlet air thermistor (Tin)
This function is used to select the
thermistor whose temperature is
shown when function P4 is set to 01.
01 Outdoor air thermistor (Tout)
02 Remote controller thermistor (RCS)
03 Remote sensor (THM4)
P4
Display of sensor
temperature
×
00 Hidden
This function is used to display the
temperature of the sensor selected
with function P3.
01 Shown
P5
Display of setting
temperature when
operation mode is
Fan
×
00 Shown
This function is used to hide the
display of setting temperature during
operation in fan mode.
01 Hidden