5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
152
Item Optional function
Individual
Setting
Settings Setting conditions Description
k5
Detection level of
the motion sensor kit
○
00 Standard (factory setting)
Models:
RPF(I)-FSN2E
Not available, use at 00 conditions.
This parameter denes the
sensitiveness of the motion sensor.
The amount of activity in the room
is assessed according to a dierent
scale based on this setting.
Detailed information about the
operation of the motion sensor
can be found in the technical
documentation of the indoor units.
01 High
02 Low
k6
Selection of allowed
operation modes
when the control
sensor of the indoor
unit is set by C8
function
○
00 All modes allowed
This function is used to select the
operation modes in which the setting
of C8 (use of remote control switch
sensor or remote sensor on THM4 to
control the indoor unit) is enabled.
01 Only cooling/dry allowed
02 Only heating allowed
03 All modes allowed
k7
Not used ○
00
- Use at 00 conditions
01
02
03
k8
Control for the
prevention of
condensation on the
louvres
○
00
Function disabled
(factory setting)
Condensation may occur around air
outlet during COOL/DRY operation
with horizontal air ow or downward
air ow for long periods.
This function is used to prevent
condensation by moving the
louvre swing angle to the third step
automatically for 30 minutes every
1 hour.
(In RPK units, this function is
activated by means of DSW2-4
instead of the K8 optional function)
01 Function enabled
kg
Not used -
00
- Use at 00 conditions
01
kA
Not used -
00
- Use at 00 conditions
01
L1
Not used ○
00
- Use at 00 conditions
01
02
03
L2
Not used -
00
- Use at 00 conditions
01
02
03