7 Servicing
RPI-(8.0-20.0)FSN3(P)E(-f) - Ducted indoor unit
SMGB0137 rev.0 - 05/2021
239
7
For RPI-(16.0/20.0)FSN3PE
? NOTE
The following procedure applies to both upper and lower fan motor groups.
1 Unscrew and remove the 7 screws of the fan motor side service cover and the 4 screws of the fan motor front service
cover.
Fan motor side
service cover
Fan motor
front service
cover
2 After removing the service covers, remove the screws which x the fan motor to its supports (4 screws at the fan
motor side service cover and 2 screws at the fan motor service cover).
Screws of
the fan motor
side service
cover
3 Remove the 4 front screws which x the fan motor group to the front side of the unit.
Front screws