7 Servicing
RPI-(8.0-20.0)FSN3(P)E(-f) - Ducted indoor unit
SMGB0137 rev.0 - 05/2021
240
4 Once the fan motor group has been released, disconnect the fan motor connector from the electrical box and pass it 
through the electrical box hole.
! CAUTION
Loosen the clamp around the fan motor connector cable to ease the release of fan motor group.
Pass the 
fan motor 
connector
through the 
hole
5 Remove the fan motor group. One person shall push the fan motor group from the position of the front service cover, 
while a second person is pulling from the position of the fan motor side service cover.
! CAUTION
The fan motor group has an approximate weight of 25 kg, and therefore removal operation shall be carried out by two persons at least.
Pull the fan motor 
group here
Remove the motor 
at this side