ModBus Data Listing
Appendix B
B–24
The table below lists the holding registers for the “F” Group Main Profile Parameters.
Note 1: When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored.
Holding Registers, “F” Group Main Profile Parameters
Func.
Code
Name R/W Description
Network Data
Reg. Range Res.
F001 Output frequency
setting
R/W Standard default target
frequency that determines
constant motor speed,
range is 0.0 / start frequency
to 400 Hz
0023h 0 / (start
freq. x 10)
to 4000
0.1 Hz
F002
(high)
Acceleration (1) time
setting *1
R/W Standard default acceleration,
range is 0.01 to 3000 sec.
0024h 1 to
300000
0.01
sec
F002
(low)
R/W 0025h
F202
(high)
Acceleration (1) time
setting, 2nd motor *1
R/W Standard default acceleration,
2nd motor,
range is 0.01 to 3000 sec.
0026h 1 to
300000
0.01
sec
F202
(low)
R/W 0027h
F003
(high)
Deceleration (1) time
setting *1
R/W Standard default deceleration,
range is
0.01 to 3000 sec.
0028h 1 to
300000
0.01
sec
F003
(low)
R/W 0029h
F203
(high)
Deceleration (1) time
setting, 2nd motor *1
R/W Standard default deceleration,
2nd motor,
range is 0.01 to 3000 sec.
002Ah 1 to
300000
0.01
sec
F203
(low)
R/W 002Bh
F004 Keypad Run key routing R/W Two options; select codes:
00...Forward
01...Reverse
002Ch 0, 1