c
OM 2012
2. Preparation for Storage
.
When a generator set is to be stored or removed from operation, special precautions
should be taken to protect the internal and external parts From rust, corrosion, and
gumming in the engine fuel system.
A. General.
.
(1) The unit should be prepared for storage as soon as possible after being removed
from service.
(2) The unit should bestored in a building which is dry and which may be heated
during winter months. ’
(3) Mo$ture absorbing chemicals are available for use where excessive.dampnes,t
is a problem, however the unit m&t be completely packaged and sealed if
moisture absorbing chemicals are to be effective,
8. Temporary Storage
When storing the unit fa.r 30 days or less, prepare as follws:
’
* (1)
: (2,
@I
. -
(4
(5)
Lubricate the unit completely in accordance wih instructions in Sect. 2-l.
This will include ohanging engine oil, and all Filter elements.,
,
Start the engine and operate for about two minutes so that .all internal
engine components will be coated with new oil e
‘.
NOTE: Do not drain the fuel system or crankcase after this run.
.-- -.-
Make &tain the cooling system antifreeze solution is adequate to protect
below the lowest temperatures expected duripg the storage period. See
271; Para. 7, D . Be sure the solution ‘a thaoughly mixed 0
Clean the exterior of the engine with Fuel oil.
Dry with clean rags and
compressed air.
Seal all engine openings.
Use a,waterproof, vaporproof material which is
strong enough to resist puncture damage From air pressures.
C. Long Time Storage (Over 30 Days)
.
(I) The unit may be stored for long periods with no special preparation if it is
possible to operate the engine once each week..
Avg 25 ‘85
Page 5