Chapter 8. PROGRAM SETUP
8-6
Setting up events 1 to 3 items
When event type is PV type event
(1) In the setting display state, move to the event 1 to 3 items of the segment to be set up
on the programming map.
(2) If you press
ENT
, the upper display starts blinking to indicate start of entry to the
No.1 setup.
(3) Press , , or to set to the No.1 setup event operating point setting.
Setting range: -1999 to 9999U
0 to 9999U (in case of absolute value deviation event)
-10.0 to 110.0% (in case of MV, MFB event)
(4) When you press
ENT
, blinking on the upper display stops.
(When
FUNC
+
CLR
are pressed, the upper display returns to “- - - -” and stops blink-
ing.)
Display (PV type event)
Operating point setting value
Program No. Segment No.
Pattern
tendency
LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out
“- - - -” is displayed for the setting values in non-set segments.
When setup data C 6 8 is set to 1, event 1 to 3 items on the programming map are
skipped and not displayed.