Chapter 4. WIRING
4-11
Before wiring, or removing/mounting the DCP301, be sure to turn the power
OFF. Failure to do so might cause electric shock.
4-9 Connecting auxiliary outputs (outputs 2, 3)
Optional auxiliary outputs can be added on.
0D, 5G, 6D auxiliary outputs
WARNING
14
15
16
17
18
19
Receiver
Receiver
Auxiliary output 1
(output 2)
4 to 20/0 to 20mAdc
Resistive load 600 max.
Auxiliary output 2
(output 3)
4 to 20/0 to 20mAdc
Resistive load 600 max.
4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.
Use shielded cable only.
2G, 3D, 5K auxiliary outputs
17
18
19
Receiver
Auxiliary output 2
(output 3)
4 to 20/0 to 20mAdc
Resistive load 600 max.
Auxiliary output 1 is not provided for 2G, 3D and 5K outputs.
4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.
Use shielded cable only.