EasyManua.ls Logo

Honeywell DCP301 - Page 172

Honeywell DCP301
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Display test (
00-02
)
Press PARA key until the display test starts.
Then, each 7-segment LED, LED indicators and LCD illuminates at every 0.5 sec.
This is to check if each LED/LCD illuminates.
Digital input test (
00-03
)
Press PARA key until the PROG/SEG display shows (
00-03
).
When you turn on or off each remote switch, the upper display will show the data
described in Table 11-4.
Table 11-4. DI
0.0.0.0.
0.0.0.1.
0.0.0.2.
0.0.0.4.
0.0.0.8.
0.0.1.0.
0.0.2.0.
0.0.4.0.
0.0.8.0.
0.1.0.0.
0.2.0.0.
0.4.0.0.
0.8.0.0.
ON
DI
Terminal
Number
Upper
Display
Notes: 1. “ON” means to short the terminals by a jumper.
2. “—” means to open the terminals.
Example:
(21)
(25)
(22)
(25)
ON
(23)
(25)
ON
(24)
(25)
ON
(41)
(25)
ON
(42)
(25)
ON
(43)
(25)
ON
(44)
(25)
ON
(45)
(25)
ON
(46)
(25)
ON
(47)
(25)
ON
(48)
(25)
ON
(21)
(25)
ON
= Short (21) and (25) terminals.
11-8
Chapter 11. CALIBRATION

Table of Contents