Specifications
*3
Loop
Rated voltage
:
8 V DC to 42 V DC
External power supply
Power supply : 9 V DC ... 30 V DC
Contact rating : max. 30 V DC / 1 A
Quiescent current : approx. 17 mA @ 12 V DC
Alarm current : approx. 18 mA @ 12 V DC
Frequency band : 868 MHz (7 channels)
433 MHz (16 channels)
Bandwidth
:
110 KHz
Modulation : FSK
Baud rate : 19,2 KBd
Transmission level : 10 mW
Range of transmission path :
up to max. 300 m
(dependent on mounting location and ambient conditions)
Ambient temperature
:
-5 °C ... +55 °C
Storage temperature : -10 °C ... +60 °C
Protection rating : IP 42
Housing : PC/ASA plastic
Colour
:
white, similar RAL 9010
Weight : approx. 250 g
Dimension
:
200 x 280 x 39 (mm) - including aerial
Specification : EN 54-17 : 2005 / -18 : 2005 / -25 : 2008
VdS approval : G 205113
Declaration of Performance : DoP-20621140331
*3
The information applies for the entire series incl. .MAR, .N0, .NU etc.