Periphery components for ESSER FACP
52 TI 798960.GB0 / 04.20
Specifications
*3
Operating voltage
:
8 V DC to 42 V DC
Batteries
:
4 batteries per 3.6 V (AA)
Batteries lifetime
:
approx. 3 years
Current consumption
:
400 µA up to max. 2.5 mA
Frequency band
:
433/868 MHz
Transmission power
:
max. 10 mW
Range
:
to max. 300 m
Usage temperature
:
-5 °C ... +55 °C
Storage temperature - without batteries
- with batteries
:
:
-20 °C ... +70 °C
+25 °C ± 10 °C
Humidity
:
95% rel. humidity (non-condensing)
IP rating
:
IP 42
Material
:
ABS-V0
Colour
:
white (similar to RAL 9010)
Weight
:
approx. 265 g (incl. batteries)
Dimensions ( x H)
:
135 mm x 88 mm, incl. fire detector
Specification
:
EN 54-17 : 2005 / -18 : 2005 / -25 : 2008
VdS approval
:
G 206091
Declaration of Performance
:
DoP-20620140331
*3
The information applies for the entire series incl. .MAR, .N0, .NU etc.