Periphery components for ESSER FACP
58 TI 798960.GB0 / 04.20
Alarm device
Alarm
Load factor
max.
Number
per loop
Visual
Audible
Speech Visual
Audible
(incl. Speech)
Total
807205R ---
--- --- 1,5-3,0 1,5-3,0
64
807205W
---
---
---
1,5-3,0
1,5-3,0
64
807214RR
--- --- 3,0-7,9 --- 3,0-7,9
32
807214WW
--- --- 3,0-7,9 --- 3,0-7,9
32
807224RR
--- 3,0-7,9 1,5-3,0 4,5-10,9
21
807224RW
---
3,0-7,9
1,5-3,0
4,5-10,9
21
807322R / -.SVxx
---
---
4,0
4,0
24
807322W / -.SVxx ---
--- 4,0 4,0
24
807372RR.xx / .SVxx
3,0-7,9 4,0 7,0-11,9
13
807372RW.xx / .SVxx
3,0-7,9
4,0
7,0-11,9
13
The load factors, FACP battery capacity, etc. can be determined using the
configuration tool at
www.esser-systems.com.
The "Maxpector VAD Selection Guide" is available at www.esser.maxpector.com for online planning
and configuration of the devices.
x
y
W / O
y
Fig. 40: W = wall mounting / signal range = height (x) x floor area (y x y)
Signal ranges visual alarm (default setting)
Classification
W-x-y
Class
W: Wall /
O: open
Installation
height
x [m]
Room width /
depth
y [m]
Light color
r: red /
w: white
Flash rate
[Hz]
Effective
intensity
Load factor
(LF)
Max. Number
of devices
W-2,4-5
W
2,4
5
r / w
0,5
6,6
3
32
W-3,2-7 W 3,2 7 r / w 0,5 13 6,2 15
W-3,6-8 W 3,6 8 r / w 0,5 17 7,9 12
OW-1,6-3,5
O 1,6 3,5 r / w 1 3,2 3 32
W2,4-5 W 2,4 5 r / w 1 6,6 5,5 17
W2,8-6 W 2,8 6 r / w 1 9,6 9,9 12
For further information on the sound pressure levels of the audible alarm, see Chap.
10.2.2 and 10.2.3.