Periphery components for ESSER FACP
60 TI 798960.GB0 / 04.20
Specifications
Operating voltage @ quiescent
:
14
V DC … 42 V DC
Operating voltage @ alarm
:
25
V DC … 42 V DC
Quiescent current @ 19 V DC
:
55 μA
Terminals
:
max. 1,5 mm
2
(AWG 30-14)
Storage temperature
:
-
25°C … +75°C
Humidity
:
95 % rel. humidity (non-condensing)
Environmental class
:
Type A (mainly for use in buildings)
Protection rating
:
IP 43 (IP 21C acc. EN 54
-3 / -23)
IP 56 with
base 806201 / 806202 (Do not use the base for acoustic alarm
applications in compliance with EN
54-3)
Calotte
:
Polycarbonate plastic,
translucent
/ partially frosted
Housing
:
Polycarbonate plastic
Colour
:
red (similar to RAL 3020) or
white
(similar to RAL 9010)
Weight
:
approx. 300 g (with back box)
Dimensions
:
Ø 112
mm, H = 78 / 93 mm
Optical
Load factor
:
3
*8
... 7,9
Flash frequency
:
0,5 Hz
*
8
/ 1 Hz
Flash colour
:
red or white
(depending on type)
Mounting
:
Wall
Signal range
:
W-2,4-5 / 60 m³
*1
... W-3,6-8 / 230 m³
Application temperature : -20°C ... +70°C
Specification
:
EN 54-23 : 2010 / -17 : 2005
VdS approval
:
G 215019
Declaration of Performance
:
DoP-21429150413
Acoustic
Load factor
:
1,5
*8
/ 3 (807205xx/-24xx)
4 (807322xx /
-72xx)
Sound pressure level
@ 90° angle
:
89 dB (A)*
8
/ 95 dB (A) (807205xx/-24xx)
95 dB (A) (807322xx/
-72xx)
Application temperature
:
-10°C ... +55°C
Specification
:
EN 54
-3 : 2001 / A1 : 2002 / A2 : 2006 / -17 : 2005
VdS approval
:
G 218071
Declaration of Performance
:
DoP
-21430171215
Combination
Load factor
:
Add values of optical and acoustic
VdS approval
:
G 218031
Declaration of Performance
:
DoP
-21431171215
*8
Factory setting, configuration with service- and programming software tools 8000.