Galaxy 3 Series Programming Manual
54
Modified Abort Operation
Hash # abort alters the standard operation so that the signalling of the intruder condition is delayed until the
end of the abort time. If the system is unset during the entry time or abort time, no alarm conditions will be
signalled.
Star º abort alters the standard operation so that if a user strays from the entry route within the entry time,
the intruder is signalled as soon as the entry deviation occurs.
NOTE 1: To comply with DD243:2002, the Standard abort operation must be used, with the abort time
set to 001 seconds.
NOTE 2: To comply with EN50131:2004 and DD243:2004, the Hash # abort operation must be used
with the Abort Time set to 30 seconds or longer.
2=Bell Delay
This option is either enabled or disabled. When enabled, it will hold off the start of any bell delay time pro-
grammed in parameter 03, until the end of the abort time programmed above.
04 = Exit Time
This parameter determines the time allowed to leave the premises via the exit route before the system sets.
The Exit Time is programmable within the range 0–300 seconds; the default is 120 seconds.
Infinite Exit Time
Assigning a value of 000 seconds sets the Exit Time to infinity; an Exit terminator activation (Final or Push-
set zone) is required to complete the setting of the system. The infinite Exit Time is normally used with a
Push-set zone to terminate the setting and an Entry zone to start the unsetting procedure.
NOTE: If the system is programmed to Autoset and the Exit Time is programmed to 000, the Exit
Time will be set to 60 seconds for the Autoset — there is no requirement for a Push-Set zone to
be activated.
Setting Multiple Groups
This parameter can be assigned a different value for each group. If more than one is group is being set, the
longest exit time is adopted for all setting groups.
51 - Parameters (cont’d)

Table of Contents

Other manuals for Honeywell Galaxy 3-48C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy 3-48C and is the answer not in the manual?

Honeywell Galaxy 3-48C Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy 3-48C
CategorySecurity System
LanguageEnglish

Related product manuals