Galaxy 3 Series Programming Manual
57
13 = PA Delay
This parameter determines the delay between the activation of a PA Delay or PA Delay Silent zone and the
alarm sounding and signalling a PA via the communicator. The PA Delay is programmable within the range
1–60 seconds; the default is 60.
This parameter can be assigned a different value for each group.
14 = Key/SW Level
This parameter assigns a code type to zones programmed as Keyswitch. The Keyswitch zone can be used
to reset system, tamper and PA alarms - depending on the reset type assigned to each of these parameters.
The default type is 3.6 - manager; the programmable range is:
• 3.7 for the engineer
• 3.8 for the remote code
15 = System Text
This parameter allows two text strings to be assigned to the system: press 1 to select the System ID or 2 to
select the Panel Location.
1. System ID — 16 character identification of system. This is used when connecting Remote Servicing
software.
2. Panel Location — 16 character message of where control is fitted.
The text is written using the alpha-numeric assembly method:
• erases characters;
• # selects upper case, lower case or library;
• A B selects alphabet character/words;
• 000–538 selects alphabet character or words;
• ent positions selected characters/words;
• esc accepts the programming and returns to the previous level; exits from the option.
16 = Soak Time
This parameter determines the number of days that zones can be soak tested for; the programmable range is
1 – 14 days; the default is 7.
NOTE: Default settings must be changed before programming in Menu Option 55 – Soak.
51 - Parameters (cont’d)