Program Zones [52] Galaxy Flex Installer Manual
108
7=Custom SIA
Use this option to change a zone’s SIA mnemonic. The default is the standard SIA
mnemonic for each zone type.
The customisable mnemonics are shown in the following table:
No Event text Description Alarm Closed Omit Unomit Troub ResTr.
Test Tamp
01 Default
02 AT/R Power AC Trouble, AC Restoral AT AR BB BU BT BJ BX TA
03 BA/R Burglary Burglary Alarm, Burglary Restoral BA BR BB BU BT BJ BX TA
04 DG/D Access Access Granted, Access Denied DG DD BB BU DT DJ BX TA
05 FA/R Fire Fire Alarm, Fire Restoral FA FR FB FU FT FJ FX TA
06 GA/R Gas Gas Alarm, Gas Restoral GA GR GB GU G GJ GX TA
07 HA/R Holdup Holdup Alarm, Holdup Restoral HA HR HB HU HT HJ BX TA
08 KA/R Heat Heat Alarm, Heat Restoral KA KR KB KU KT KJ BX TA
09 LT/R Line Fail Line Trouble, Line Restoral LT LR BB BU BT BJ BX TA
10 MA/R Medical Medical Alarm, Medical Restoral MA MR MB MU MT MJ BX TA
11 PA/R Panic Panic Alarm, Panic Restoral PA PR PB PU PT PJ BX TA
12 QA/R Assist Emergency Alarm, Emergency Restoral QA QR QB QU QT QJ BX TA
13 RO/C Relay Relay Open, Relay Closed RO RC BB BU BT BJ BX TA
14 SA/R Sprinklr Sprinkler Alarm, Sprinkler Restoral SA SR SB SU ST SJ BX TA
15 TA/R Tamper Tamper Alarm, Tamper Restoral TA TR TB TU BT BJ TX TA
16 WA/R Water Water Alarm, Water Restoral WA WR WB WU WT WJ BX TA
17 YT/R Battery Battery Alarm, Battery Restoral YT YR BB BU BT BJ BX TA
18 ZA/R Freezer Freezer Alarm, Freezer Restoral ZA ZR ZB ZU ZT ZJ BX TA
19 UA/R Keysafe Keysafe opened, Keysafe closed UA UR UB UU UT UJ BX TA
Table 4 Customisable Mnemonics
Note: If two zones, programmed as Custom SIA (with the same type assigned, e.g. both
WA/R) activate within the confirm time window in SET or UNSET condition, a
CONFIRM is logged.
8=Activity Mon.
Use this attribute to check a zone’s activity during a set time period or set/unset cycle. The
options are:
0=None (default), 1=Type1, 2=Type2, 3=Type3, 4=Type4, 5=Type5, 6=Type6
If the zone does not activate at least once within the programmed criteria a zone masked
fault is indicated at the panel. The fault is logged as a masked event indicating that the zone
has been inactive for the programmed period. Refer to Activity Monitoring [51.61].
9=Res. Select
See Resistance Select [51.46].