Full Test [62] Galaxy Flex Installer Manual
166
Full Test [62]
Use this option to select and test two zones under full set conditions. Activating the selected
zone results in a full alarm condition, including remote signalling. Constantly active zones
(Security, PA, and Fire) remain active throughout the Full Test. An activation generates the
appropriate local or full alarm depending on the zone.
To start the full test:
1. Select the Full Test option. The address and function of the first zone on the system is
displayed.
2. Navigate to the required zone, and then press ent.
3. An option is then given to choose a second confirm zone.
If you press A (YES), select a second required zone by pressing ent.
If you press B (NO), the system begins the full setting procedure. Activating the
zone results in a full alarm condition.
To end the full test:
U
nset the system.