EasyManua.ls Logo

Honeywell Galaxy Flex V3 Series - Connect Outputs; Secure the Tamper Circuits

Honeywell Galaxy Flex V3 Series
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connect outputs Galaxy Flex Installer Manual
20
The wiring of the terminator and keyswitch zone type is shown in the following figure:
Figure 7 Terminator and keyswitch zone wiring
Connect outputs
Outputs are addressed in the same way as the zones. If using on-board outputs, connect and
a
ddress as follows:
O/P Address Function O/P type Connection
1 1001 Bells Open-collector,
switched negative
Connect load between OP1
and +12 V
2 1002 Strobe Open-collector,
switched negative
Connect load between OP2
and +12 V
3 99 Exit/Entry (E/E) horn AC audio to drive an
internal loudspeaker
Connect load (8–32 )
between OP3 and +12 V
If required, use the Program Outputs menu (53 ent) to modify the default settings.
Figure 8 A typical application
Secure the tamper circuits
1. If
an external siren/bell/warning device is fitted, connect the tamper return line from the
device to the T terminal.
2. If an external siren/bell/warning device is not fitted, connect the T terminal directly to
the 0 V terminal.
3. If a relay output is required, fit the Output Option Board.
4. Replace and secure the panel cover.

Table of Contents

Related product manuals