Galaxy Flex Installer Manual Parameters [51]
89
If the Local Part parameter is set to 1 (enabled) the Intruder outputs activate if an alarm
condition occurs when the system is part set.
Option 2 (SIA part off) is identical to option 1 with the exception that when the alarm
format of the telecom module is set to SIA, part setting and unsetting of the system is not
signalled to the ARC. You can assign a different value to each group.
Banner [51.12]
Use this option to customise the top and bottom lines of the banner display.
Press 1 to select the TOP LINE or 2 to select the BOTTOM LINE. The display is written
using the alpha-numeric assembly method:
î erases characters.
# selects upper case, lower case or library.
A and B can be used to scroll through alphabet characters or words.
001â538 select alphabet character or words from the library using a number code.
ent positions selected characters/words.
esc accepts the programming and returns to the previous level.
The banner is displayed when the system is in the normal mode (set/unset).
PA Delay [51.13]
Use this option to set the delay between the activation of a PA Delay or PA Delay Silent
zone and the alarm sounding and signalling a PA via the communicator.
The default is 60 seconds and the range is 1 to 60 seconds.
You can assign a different value to each group.
Key/SW Level [51.14]
Use this option to assign a code type to zones programmed as Keyswitch. The Keyswitch
zone can be used to reset system, tamper and PA alarms, depending on the reset type
assigned to each of these parameters. The default type is 6 (manager) and the programmable
range is 0 to 7 (7 for the engineer).