Galaxy Flex Installer Manual Parameters [51]
95
To select a preset, enter an option number from the tables below:
Option Double balanced End of line Split resistance
01 1k - -
02 - 1k -
03 2k2 - -
04 - 2k2 -
05 4k7 - -
06 - 4k7 -
07 5k6 - -
08 - 5k6 -
09 3k3 - -
10 - 3k3 -
11 1k fault - -
12 - 1k fault -
13 1k N/O - -
14 - 0k N/C -
15 - - 2k2, 4k7
16 2k - -
Table 2 Resistance values
The operating range for each resistance value is shown in Appendix H: Resistance tables on
page 255.
When a preset is selected it sets the zone resistance range used by every zone on the system.
Each zone on the system can be further customised to a specific preset by using the
Resistance Select [52.9] option.
Set Confirm [51.47]
Use this option to cause the system to emit a short double beep when the system/group has
set. There are three options:
0=Off No indication.
1=Alert on Set A double beep when the system has set.
2=Alert on Comm A double beep after a successful signal to the ARC that setting has
occurred.
Alarm Limits [51.48]
Use this parameter to program the maximum number of alarms, per group, which may be
transmitted to an Alarm Receiving Centre in any set period. There are three options:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Flex V3 Series and is the answer not in the manual?

Honeywell Galaxy Flex V3 Series Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy Flex V3 Series
CategorySecurity System
LanguageEnglish

Related product manuals