GSMV4G/GSMVCN4G Installation and Setup Guide
3-16
PROMPTS
ZONE
2-4204
OPTIONS DESCRIPTION
41
Rpt Zn3 ONLY if
Armed (N)_
X X
Reports alarms on zone 3 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to "Report
Only if Armed," skip to Prompt 52: "Enable Zn6."
42
Zn4 Trigger Type
(V+)_
X
• (V+)
• (V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
43
Invert Zn4 Y/N
(N)_
X
Inverts the alarm and normal states of the zone 4
trigger; otherwise uses normal input signal.
44
Restore Zn4 Y/N
(Y)_
X X
[Y], [N] Enables restore reporting for zone 4.
UL/ULC: Must be set to “Y.”
45
Delay Zn4 (secs)
(00)
X X
[00] = no delay
Defines the reporting delay in seconds for
zone 4.
UL/ULC: Must be set to “00.”
46
Rpt Zn4 ONLY if
Armed (N)_
X
2-
4204
only
Reports alarms on zone 4 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-4204
mode) is triggered (armed).
If [N], always reports alarms on zone 4.
47
Zn5 Trigger Type
(V+)_
X
• (V+)
•
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
48
Invert Zn5 Y/N
(N)_
X
Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.
49
Restore Zn5 Y/N
(Y)_
X
4204
Enables restore reporting for zone 5.
UL/ULC: Must be set to “Y.”
50
Delay Zn5 (secs)
(00)_
X
2-
4204
only
[00] = no delay
Defines the reporting delay in seconds for
zone 5.
UL/ULC: Must be set to “00.”
51
Rpt Zn5 ONLY if
Armed (N)_
X
2-
4204
only
Reports alarms on zone 5 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-4204
mode) is triggered (armed).
If [N], always reports alarms on zone 5.
52
Enable Zn6 Y/N
(N)_
4204
only
Enables alarm reporting for zone 6.
If [N], skip to Prompt 58: "Enable Zn7."
53
Zn6 Trigger Type
(V+)_
X
4204
only
•
• (V+)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
54
Invert Zn6 Y/N
(N)_
X
4204
only
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
55
Restore Zn6 Y/N
(Y)_
X X
Enables restore reporting for zone 6.
UL: Must be set to “Y.”
56
Delay Zn6 (secs)
(00)_
X X
[00] = no delay
Defines the reporting delay in seconds for
zone 6.
UL/ULC: Must be set to “00.”