The flame simulation check is conducted after applying
the start-up signal (
) during the waiting time t
W
.
Start-up signal, safety interlock
The start-up signal is the same as the signal in the
safety interlock.
If the start-up/safety interlock signal drops more than
four times in succession during start-up, an inadmissible
quantity of non-combusted gas can reach the combus-
tion chamber during the safety time via open gas valves.
Therefore, a fault lock-out is performed on the automatic
burner control unit IFD 258 following three consecutive
drops of the start-up/safety interlock signal (blinking
).
If flame simulation is signalled during start-up, the flame
simulation delay time t
LV
starts to elapse. If the flame
simulation is discontinued during the flame simulation
delay time t
LV
(max. 25 s), the burner will start up. Oth-
erwise, a fault lock-out occurs. The display blinks and
indicates .
t
W
1
. . .
88
V1
t
01
01
1
L1
3
10
11
5
1314
89
t
W
t
t
LV