The IFD is equipped with two signalling contacts for 
operating and fault signals. For controlling two-stage 
burners, a bridge must be installed in the lower section of the 
housing between terminals 12 and 13. Valve V2 is connected 
to terminal 14.
 
gas valve V1 and ignites the burner. The ignition time t
Z
 is 
constant. The safety time t
SA
 starts with the igni-
 
tion time t
Z
. If a flame is detected during the safety time, the 
operation signalling contact closes and valve 2 is opened once 
the safety time t
SA
 has elapsed.
 
If no flame is detected, the fault signalling contact clos- es 
once the safety time t
SA
 has elapsed.
 
Example  of application
 
Control: ON/OFF or ON/HIGH/LOW/OFF
 
The burner BIO/BIC starts at low-fire rate. Once the normal 
operating state is reached, the automatic burn- er control unit 
IFD 258 opens the air valve. The burner switches to high-fire 
operation.
 
 
 
 
Program sequence
 
During the waiting time t
W
 after heat demand, checks are 
made for flame simulation and fail-safe operation. If no flame 
simulation is detected, the IFD 258 opens the
 
1    2   3   4  5   6   7   8   9  10  11  12  13 14 
max.
 
 
  GIK..B 
 
VAS 
BIO/
 
BIC 
VR..R