Parameter 14
 
This indicates the safety time during operation t
SB
 
for valves V1 and V2. The default in accordance with 
EN 298 is 1 s. The IFD is also available with a safety
 
time during operation t
SB
 of 2 s. Prolonging the time in- 
creases the installation availability in the case of brief- 
duration signal fades (e.g. fades of the flame signal).
 
In accordance with EN 746-2, the safety time of the 
installation during operation (including closing time of 
the valves) may not exceed 3 seconds (note the require- 
ments of the Standards).
 
4
 .
4
 .
2
 
F
aul
t
 
l
o
c
k
-
o
u
t
 
or
 
re
s
t
ar
t
 
Parameter 12
 
A switch on the underside of the upper section of the 
housing determines whether the IFD starts a one-off 
restart or performs an immediate fault lock-out for the 
burner after a flame failure, see page 29 (Behaviour
 
in the event of flame failure).
 
Immediate fault lock-out following flame failure
 
Parameter 12 = 0,
 
Switch in fault lock-out position   :
 
 
 
After a flame failure during operation, the IFD 258 will 
perform a fault lock-out within the safety time during 
operation t
SB
 (the safety time during operation t
SB
 is 
1 second. The IFD 258 is available with a safety time 
of 2 seconds upon request). At the same time, the gas
 
valve is closed. The fault signalling contact closes and 
the display blinks and indicates 
04 
, see page 16 
(Program status and fault messages).
 
After a fault lock-out, the IFD 258 can be reset, either 
by using the button on the front panel or an external 
button. Several automatic burner control units can be 
reset in parallel using the external button. The IFD 258 
cannot be reset by mains failure. The fault signalling 
contact does, however, open as soon as the mains volt- 
age fails.