Several automatic burner control units can be reset in 
parallel using the external button. The IFD 258 cannot 
be reset by mains failure. The fault signalling contact 
does, however, open as soon as the mains voltage fails.
 
7
 .
8
 
R
e
mo
te
 
re
s
e
t
 
Permanent
 
The unit can no longer be reset by permanent remote 
reset: if a remote reset signal is permanently applied to 
terminal 4,  flashes on the display as a warning sig-
 
nal. The IFD continues operation until it locks  off.
 
Automatic (PLC)
 
Check whether automatic remote reset (PLC) complies 
with standards (reset for no longer than 1 second).
 
If a fault is acknowledged by remote reset too often, 
flashes on the display to indicate a fault (too many re- 
mote resets). The error can only be acknowledged with 
the Reset/Information button on the unit.
 
The burner malfunction must be remedied. The mal- 
function cannot be remedied by changing the method 
of activation.
 
7
 .
9
 
B
e
h
a
v
i
o
u
r
 
i
n
 
t
h
e
 
eve
n
t
 
o
f
 
fla
m
e
 
fa
i
lu
re
 
In the event of a flame failure, either a restart or an 
immediate fault lock-out can be selected using a switch 
in the upper section of the automatic burner control 
unit IFD 258.
 
Restart
 
Select for burners that occasionally demonstrate un- 
stable  flame behaviour.
 
Immediate fault lock-out
 
Select an immediate fault lock-out when using the 
unit with slow-closing air control valves or continuous 
control, if the burner may not be started at maximum 
capacity, for burners with a capacity of over 120 kW in 
accordance with EN 676 and in the case of On/Off in- 
termittent operation.