In the case of multiple burner applications, burners
with forced air supply are used. The air for combustion
and pre-purge is supplied by a central fan controlled
by a separate logic. This logic determines the purging
time and controls an external relay that switches the air
valve to purge.
The automatic burner control unit must not be activat-
ed during purging. This is achieved by interrupting the
safety interlock, amongst other methods.
7
.
4
E
m
er
g
e
n
c
y
s
t
o
p
i
n
t
h
e
eve
n
t
o
f
fi
re
or
electric shock
If there is a risk of fire, electric shock or similar, inputs
L1, N and 3 (start-up/safety interlock signal) of the IFD
should be disconnected from the electrical power sup-
ply.
Important!
This should be reflected in the wiring on
site!
7
.
5
E
m
er
ge
nc
y
s
t
op
t
r
i
gge
re
d
b
y
s
af
e
t
y
interlock
The safety interlock turns off the power to the input 3
(start-up/safety interlock signal), such as in the event of
air deficiency or similar.
7
.
6
O
ver
l
o
ad
pr
o
t
e
c
t
i
on
To protect the unit against overload by frequent cycling,
only a specific number of start-up attempts can be car-
ried out by the IFD. The maximum number of start-up
attempts per minute depends on the safety time t
SA
and the ignition unit.
t
SA
[s]
t
Z
[s]
Type of ignition
Cycle lock
[s]
3
1.8
External TZI
10
5
3
External TZI
12
10
6
External TZI
15
3
1.8
IFD..I
36
5
3
IFD..I
60
10
6
IFD..I
120
If too many start-up attempts are made, flashes on
the display to indicate a fault.
13
14
5
GIK..B
VAS
BIO/
BIC
VR..R
N
11
10
Purge