LYNX Touch Installation and Setup Guide
- 64 -
Agency Notices
1. For Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60
seconds. For Burglar Alarm installations without line security, total exit delay time must not exceed
120 seconds.
2. Periodic testing must be at least every 24 hours.
3. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for ETL installations.
4. Auto-disarming is not a ETL Listed feature.
5. As SIA limits for delay of alarm reporting and sounding can exceed UL Standards for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the
alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
SIA Quick Reference Guide
Programming Section Feature Range Shipping Default SIA Requirement
Installation and Setup Guide or Programming Guide
Reporter/
Report Selection
Exit Error Enabled or Disabled Enabled Enabled
Recent Closing Enabled or Disabled Enabled Enabled
Alarm Cancel Enabled or Disabled Enabled Enabled
Reporter/Options
Call Wait Cancel Enabled or Disabled
Field is blank (a PBX prefix
is entered to enable)
Enabled if User has call
waiting
Number of Reports 1 to 6 Reports 2 Reports 2 Reports
Alarm Report Delay
(Abort Window)
15, 30 and 45 seconds 30 Seconds 30 Seconds*
System Settings
Entry Delay # 1
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or 4
minutes
30 Seconds 30 Seconds minimum
Entry Delay # 2
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or 4
minutes
30 Seconds 30 Seconds minimum
Exit Delay
45, 60, 90 seconds and 2
minutes
60 Seconds 45 seconds minimum
Restart Exit Time Enabled or Disabled Yes (Enabled) Enabled
Exit Warning Not selectable Always enabled Enabled
Auto Stay Arming Enabled or Disabled Yes (Enabled) Enabled
Cross Zone Delay
30 seconds and 2 minutes
(in 30 second increments),
3 minutes and 4 minutes
None (Disabled)
Enabled and two zones
programmed
Zones
Fire Alarms
Zone Type “Fire with
Verification” must be
selected for Fire Zone 95
Disabled Disabled
User Guide
User Functions/
User Access
Duress
Duress Code is
Programmed by Master
User as User 16
Disabled Disabled
System Functions/
Testing the System**
System Test
System tests provided as a
User Function
n/a n/a
Communications
While the system is in Test
mode, no alarm reports are
sent to the Central Station
Disabled Disabled
* Combined Entry Delay and Alarm Report Delay (Abort Window) should not exceed 1 minute.
** Refer to the User Guide for procedures on Testing the System.
Note: Using the Call Waiting Cancel feature on a non-Call Waiting line will prevent successful communication to the Central Station.