Page 34 Document No. 996-175-000-1, Revision 01 Commissioning Manual
5.4.2.8 Pattern PULSE-ON-ON
[ Panel in Commissioning mode ]
---------------------------------------------
Pattern zone 1/2 Sensors
3 001 to 080 PULSE/ON -> ON 120s
RESULT: Sounder circuit A will turn on if two or more detectors have gone into fire in zone 1, or two or
more in zone 2 etc. If only one detector is in fire the sounder will pulse.
The configuration shown on the display becomes effective immediately after the ‘Enter’ or ‘Yes’ key is
pressed. Pressing the ‘No’ key will abort the operation and return to the commissioning menu.
The ‘Yes’ key also automatically advances to the next zones to be defined.
Zone 1 Call Point
in Alarm
Zone 1 Sensor 1
in Alarm
Zone 2 Sensor 1
in Alarm
SOUNDERS
PULSE
SOUNDERS
PULSE
SOUNDERS
ON
SOUNDERS
ON
120 s
Zone 1 Sensor 2
in Alarm
No Action No Action
Pattern
Validated
5.4.3 Detector Loop Addressable Sounder Circuit Controller Units (SCC)
One or more addressable sounder controller units may be included on each loop of the system. Refer
to the relevant manufacturer’s literature for precise details on how to wire these devices.
Open and short circuits on the sounder wiring are detected by the SCC module, logged, and displayed by
the control panel. Wiring faults on the loop are also detected by the panel and again logged and displayed.
Any SCC connected to the system can be configured to sound for fires in ANY zone in the system.
When SCC units are used, their zone programming selection is shown by using the same ‘Sounder’
configuration option as the on-board outputs. For example, an SCC module wired onto loop 2 at
address number 117 may be shown as:
[ Panel in Commissioning mode ]
---------------------------------------------
SOUNDER Pattern
2:117_a 001
This shows all sounders wired into the SCC module located on loop 2 at address 117 will use ringing
pattern number 1.
From Version 828 Onward
When using an Hochiki CHQ-AB beacon device in combination with a CHQ-BS base
sounder (using the same address), both devices may have independent pattern settings.
Settings associated with the CHQ-AB will be displayed with a suffix ’a’ appended to the
address e.g. ‘2:117_a’ and CHQ-BS with a suffix ‘b’ e.g. ‘2:117_b’.
5.4.4 Peripheral Loop Addressable Sounder Circuit Controller Units
Up to 15 4-way sounder cards can be added to the system via the RS485 peripheral loop.
These sounders are programmed in the same way as the other sounders.