ZX Fire Alarm Control Panels MORLEY-IAS
Commissioning Manual Document No. 996-175-000-1, Revision 01 Page 39
8 Program Integrity Option
This option shows the status of the system memory.
To select the Program Integrity option, press ‘2’ from page 2 of the Commissioning Menus. The
display then shows the status in the following format:
[ Panel in Commissioning mode ]
---------------------------------------------
*Program OK . Config RAM UNLOCKED *
8XX-MXXX 01B6D05B 66BE0B22
The top line shows the status of the ROM (Program Memory) and RAM (Configuration Memory).
The ROM status will show either ‘Program ok’ or ‘Program FAIL’ depending on the calculation of the
checksum.
Should the ROM status indicate a failure, it is important to contact the factory immediately.
Please make a note of the software version number and ROM checksum displayed.
The RAM status will show as PASS, UNLOCKED or FAIL.
If the display indicates a Configuration Memory failure, perform the following actions and
recheck.
Set the memory lock switch to OPEN, select and then exit from the CONFIG option (page
1 of the commissioning menus, set the memory lock switch to LOCK and select NORMAL
OPERATION. Then re-check the Program Integrity.
The bottom line of the display shows three parameters. These are, from left to right, the software
version code (8XX-MXXX shown here is typical of MIAS 800 Series panel software), the ROM
checksum and the RAM checksum. The ROM and RAM checksums are in hexadecimal notation and
the examples shown are typical of the type of hexadecimal data displayed here.
The ROM version and checksum are not alterable and should be quoted in all correspondence.
The RAM checksum will alter whenever the configuration is changed. For example, the figure will
change when either adding or removing devices, changing text assignments, etc.
When the configuration has been changed, the program integrity should be checked and
the RAM checksum should be recorded.
8.1 Program a Panel from a PC Using the ‘FIRE’ Program
The distribution disk also contains previous versions of PC programs. The following table shows the
panel software versions supported by each program on the disk.
Program File name (on distribution disk)
Software version Fire Panel program
FIRE6 Windows versions 6.16 From 760 to date
FIRE5.EXE 5.06 From 601 to 706
FIRE4.EXE 4.31 548 to 565
Table 9 - PC Programming tool - software compatibility