MORLEY-IAS    ZX Fire Alarm Control Panels
 
 
Page 2  Document No. 996-175-000-1, Revision 01   Commissioning Manual 
 
CAUTION: A Lithium Battery is used for Data Retention. 
Replace only with the same or equivalent type. Contact the Service Organisation for 
Replacement. 
 
This symbol identifies that the panel uses a safety isolating mains transformer. 
 
 
1.3 National Approvals 
 
This equipment must be installed and operated in accordance with these instructions and the 
appropriate national, regional and local regulations specific to the country and location of the 
installation. Consult with the appropriate Authority Having Jurisdiction (AHJ) for confirmation of the 
requirements. 
1.4 EN54 Information 
 
EN54
!
 
EN54-2 13.7 
Maximum of 512 
sensors / manual 
call points per 
panel. 
•  The ZX1Se, ZX2Se, ZX5Se and ZX10Se range of panels has many 
features, which if used inappropriately, may contravene the 
requirements of EN54. Where such a possibility may arise, a suitable 
warning is given with brief details of the EN54 requirement and the 
relevant section it pertains to. A typical EN54 non-compliance 
warning is illustrated. 
 
 
EN54
 
•  This Fire Control Panel complies with the requirements of EN54-2/4 1997. In addition 
to the basic requirements of EN54, the panel conforms to the following optional 
functions. 
 
Option EN54-2 Clause 
 
Indication:  Fault signals from points 
Controls: Coincidence Detection 
  Delays of Actioning Outputs 
  Disablement of each address point. 
 Test condition 
Outputs:  Outputs to fire alarm devices   
8.3 
7.12 
7.11 
9.5 
10 
7.8 
 
 
EN54
 
•  The power supplies for the ZX1Se, ZX2Se, ZX5Se and ZX10Se range of panels 
complies with the following clauses of EN54-4. 
 
Power Supply Functions  EN54-4 Clause 
 
Derive power supply from main power source 
Derive power supply from a standby battery source 
Charge and monitor the standby battery source 
Detect & signal power supply faults 
5.1 
5.2 
5.3 
5.4