ZX Fire Alarm Control Panels MORLEY-IAS
Commissioning Manual Document No. 996-175-000-1, Revision 01 Page 7
Indicator Colour Function How to Clear
FIRE
Red The panel has detected a fire alarm
condition, or the ‘Sound Alarms’ key
has been pressed.
Identify and correct the condition
causing the alarm and then perform
a panel reset.
Fault
Yellow The panel has detected a fault. Correct the condition causing the
fault and then perform a panel reset.
Acknowledged
Yellow A fault or alarm has been
acknowledged and the internal
buzzer silenced.
Correct the condition causing alarm
or fault and then perform a manual
reset. NOTE: If another alarm or fault
occurs, the internal buzzer
automatically resounds.
Disablement
Yellow Part of the system, either input or
output, has been disabled manually
by the user.
Re-enable the device or devices.
Refer to Disablement Function.
Test
Yellow The system is in test mode. Zone
LED indicators show which zones
are being tested.
Cancel test when finished.
Sounder Fault
Yellow This indicates a wiring fault with one
of the sounder output circuits.
Correct the fault condition and then
perform a panel reset.
Delayed Mode
Yellow This indicates that the system is
operating with delays to the sounder
outputs and the delays are active (in
force).
The delays may be enabled or
disabled. Refer to Disablement
Function.
Relays Disabled
Yellow The relay outputs have been
disabled.
Refer to Disablement Function.
Earth Fault
Yellow An earth connection fault has
occurred on a cable.
Correct the fault condition and then
perform a panel reset.
System / CPU Fault
Yellow The CPU has reset or a system fault
has occurred.
Correct the problem, if appropriate,
and then perform a panel reset.
Sounders Disabled
Yellow
Some or all of the sounder
1
outputs
have been disabled.
Refer to Disablement Function.
Alarms Silenced
Yellow
The sounder
1
outputs have been
silenced.
Correct the alarm condition and then
perform a panel reset. NOTE: Press
SILENCE / RESOUND again to
reactivate the sounders. If a new
alarm occurs, the alarms will
resound.
Supply Fault
Yellow There is a problem with the power
supply, battery or supply input.
Correct the fault condition and then
perform a panel reset.
Power
Green STEADY: Indicates AC Power is
present. FLASHING: Indicates a loss
of AC Power.
See Supply Fault.
Zone FIRE
Red FLASHING: The zone is in a fire
alarm condition.
Correct the alarm condition and then
perform a panel reset.
Zone Fault
Yellow FLASHING: The zone contains faulty
devices.
STEADY: The zone is either disabled
or in test mode.
Correct the fault condition and then
perform a panel reset.
Re-enable devices or cancel test
mode.
Table 3 – LED Functions
1
This includes loop-based sounders.