ZX Fire Alarm Control Panels MORLEY-IAS
Commissioning Manual Document No. 996-175-000-1, Revision 01 Page 43
NOTE: Only one mode of operation can be selected to be operational at one time.
11.2 Delayed Mode
EN54
!
EN54-2 7.11
Delays to Outputs
The panel can be configured to operate in a delayed mode
during the daytime in any specified zone.
During this time, high sensor signals will generate a fire
message at the panel, but delay the output to the sounders. The
panel will initiate a full fire alarm if action is not taken on this
warning within a specified time.
Manual call points (Pull Stations) will always generate an
immediate fire alarm, regardless of any day mode setting.
Ensure that at least one sounder circuit is configured for immediate
operation when the fire alarm is confirmed (end of stage 2 time).
Ensure that the fire output relay is configured with the
appropriate pattern so that it does NOT turn on until the fire
alarm is confirmed (end of stage 2 time).
11.2.1 Commissioning Delayed Mode
Press ‘1’ to select Delayed mode from the Day Mode Menu. The display will prompt whether the mode
is to be used.
[ Panel in Commissioning mode ]
---------------------------------------------
Allow mode ?
Press ‘No’ to inhibit the mode and return to the Day Mode menu.
Press ‘Yes’ to enable the mode. The display will then prompt the start and end times for the day period.
[ Panel in Commissioning mode ]
---------------------------------------------
START at 08:45 ?
Press ‘Yes’ to accept and step on. Press ‘No’ to change and then enter the required start time using
the number buttons.
[ Panel in Commissioning mode ]
---------------------------------------------
START at 08:45 FINISH at 16:35 ?
Press ‘Yes’ to accept and step on. Press ‘No’ to change and then enter the required end time using the
number buttons. Note: the delay mode will remain active for the extent of the ‘FINISH at’ minute.
A two-stage timer is built into the day mode.
After entry of the start / end times, the display prompts the stage timers as follows: