EasyManuals Logo

Honeywell MS-5UD Series User Manual

Honeywell MS-5UD Series
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
Programming
100 MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
3.5.5.4.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel
will not answer an incoming call. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The
following screen will be displayed:
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring
count which can be a value between 00 and 25. After the second digit is entered, the display
will return to the Service Terminal screen.
3.5.5.4.5 Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2
by the DACT when using an alternate means of secondary transmission path. The factory
default setting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the
following screen to be displayed:
Each press of the 1 key while viewing this screen will toggle the option between Supervise
Phone Line 2 Yes and No.
3.5.6 History
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 3 while viewing Programming Screen #2 will display the History options
as shown in the following display:
SERVICE TERMINAL
1=RING COUNT
Service Terminal Screen #2
RING COUNT
RANGE 00-25 RINGS
Ring Count Screen
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen #2
SUPERVISE PHONE LINE
1=PHONE LINE 2 YES
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell MS-5UD Series and is the answer not in the manual?

Honeywell MS-5UD Series Specifications

General IconGeneral
BrandHoneywell
ModelMS-5UD Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals