Programming
102 MS-5UD/MS-10UD Series   PN 52626:B  8/01/2008
3.5.7 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset the control 
panel after each device activation.  Refer to the sections titled  "Walktest" on page 106 and  
"Walktest" on page 117 for additional information regarding the Walktest feature.  Pressing 1 while 
viewing the Programming Screen #3 will cause the following Walktest options to be displayed:
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest 
Screen.  To perform an audible walktest, which will sound the NACs, press 2 while viewing the 
Walktest Screen.  When either option is chosen, the panel will enter Walktest Mode and the 
following screen will be displayed:
The user can now perform a one-person walktest by activating devices throughout the system.  As 
each device is activated, the screen will display the information about the activated device as shown 
below.  Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the 
walktest screen from an actual alarm screen.  
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to 
the Walktest Screen.  The results of the Walktest can now be viewed by pressing 3 while viewing 
the Walktest Screen.  The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed as 
illustrated in the preceding screen.  Note that the Walktest log is stored in RAM.  If all power (AC 
and DC) is removed from the FACP, the Walktest log information will be lost.  This information is 
also overwritten when subsequent walktests are performed.
    PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
     WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen  
 
 UNIT IN WALKTEST
Walktest Active Screen  
ALARM ZONE 1
     <ADJ> <NOUN>
               Z01
 10*00A 010805 
  WALKTEST RESULTS