42 ACPS-610/E Manual — P/N 53018:A1 07/31/2007
Applications Synchronization
Figure 4.5 Supervised Synchronization Wiring Using UZC-256
FACP
SLC
SLC to Next Device
UZC-256
NO
COM
NO
NC
NC
COM
SLC
UZC-256 Sync Feeder
ACPS-610
ACPS-610
ACPS-610
-
P/N
ELR-2.2K
(2.2 K ohm
end-of-line
resistor),
included
NOTES:
Do not use visual devices on coded NAC outputs.
Do not put NAC devices on the UZC-256 Sync Feeder.
The wiring from the FACP shall be within 20 feet (6.1 m) in conduit in the same room. See the
UZC Installation Manual for more information on the applications that require power
supervision.
The UZC-256 is compatible with Notifier control panels except the AFP-100 and AFP-200.
50 ohm maximum loop resistance per sync riser. (Figure 4.5 shows one sync riser.)
For more information, see Figure 4.6.
-
+
-
+
P/N
ELR-2.2K
(2.2 K ohm
end-of-line
resistor),
included
SLC
+
-
+
-
+
-
-
+
+
P/N
ELR-2.2K
(2.2 K ohm
end-of-line
resistor),
included
P/N ELR-2.2K
(2.2 K ohm
end-of-line
resistor),
included
+24V power
source
+
-
The wiring from the FACP shall be within 20 feet (6.1 m) in conduit
in the same room. See the UZC Installation Manual for more
information on the applications that require power supervision.
ALARM POLARITIES SHOWN
-
+
-
+
Sync Riser
ACPS-610_UZC.cdr