ID2000 Series Operating Manual
Appendix 1
A1 - 10997-434-000-4, Issue 4
May 2010
PANEL STATUS: TEST
This is the condition of the panel when a Zone has been
selected for a walk test, using the appropriate pushbutton
sequence (see Section 4.8.1 for details).
The TEST condition continues to be shown until
superseded by a higher-priority condition or until Test
mode is terminated using the appropriate pushbutton
sequence.
The LCD displays the message shown below:
The indications of the panel and external equipment are
as follows.
LAMP indications:
POWER (green): ON
TEST (amber): ON
All other LAMPs OFF
Numbered zone indication (amber) STEADY
Internal sounders and
Circuits Controlled Internally: as for status NORMAL
External Devices:All CONTROL MODULES
should be OFF
The built-in LED indicators on the sensor(s) in the Zone
in test show 1-second-ON/1-second-OFF pulses
(possibly with intervening short pulses).
The built-in LED indicators on all other sensors and
modules should either give short pulses or be OFF
altogether, as configured.
(ZONE or device (no)) IN TEST (date) (time)
(blank) or (System Normal message) or (last tested device)