ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
65
997-263-000-11, Issue 11
January 2010
5.5.5.5 Heat Det. End Delay
The Day Mode function, Delays to outputs, can be
cancelled when a heat sensor goes into alarm. To select
the Heat Det. End Delay option:
1 From the Setup menu screen, press the ‘
5
’ button
on the numeric keypad to enter the Day/Night Settings
menu. The Day mode activity screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Day/
Night Settings options until the Heat Det. End Delay
screen is displayed.
3 Press the ‘
6
’ button to toggle this function.
4 Press ‘
4
’ to exit and return to the Setup menu
screen. The selection is saved on exiting.
5.5.5.6 Day Mode 2 Zone Ends Delay
The Day Mode function, Delays to outputs, can be
cancelled, through this Day/Night Settings option, by a
second zone going into alarm. This is an alternative to a
second device in the same zone going into alarm or the
activation of an MCP cancelling active delay timers.
To select the Day Mode 2 Zone Ends Delay option:
1 From the Setup menu screen, press the ‘
5
’ button
on the numeric keypad to enter the Day/Night Settings
menu. The Day mode activity screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Day/
Night Settings options until the Day Mode 2 Zone Ends
Delay screen is displayed.
[S1 Setup] 4: Peripheral Options
5: Day / Night Settings ¦ : More
[S1 Setup] 1: Panel Options
2: Site Details 3: Device Options ¦ : More
[Setup] Heat Det. End Delay = No
> : Change ¦ : More < : Exit
[Setup] Heat Det. End Delay = Yes
> : Change ¦ : More < : Exit
6
or
8
2
[S1 Setup] 4: Peripheral Options
5: Day / Night Settings ¦ : More
[S1 Setup] 1: Panel Options
2: Site Details 3: Device Options ¦ : More
[Setup] Day Mode 2 Zone Ends Delay = No
> : Change ¦ : More < : Exit
or
82
5
[Setup] Day mode activity = DISABLED
> : Change 1 : Disable ¦ : More < : Exit
5
[Setup] Day mode activity = DISABLED
> : Change 1 : Disable ¦ : More < : Exit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals