Revision 1 SLN 700 SmartLine NCR Level Transmitter User’s Manual Page 39
Error Codes:
Following are the details of error codes with respective resolution. The error codes will show
up on display screen during malfunction/error condition in device
Error
Code
Description
Solutions
1 Communication error between display
and module
Need new display module
2 EEPROM Error Return to Factory
3 PLL Failed, RF circuit failure Return to Factory
4 Internal Operation Error or use during
development, internal use only)
Return to Factory
5 Internal Command Error for use during
development, internal use only)
Return to Factory
6 Authentication Failed Return to Factory
7 SysBusy Restart, if problems persist return unit to
Factory
8 Low Power Low power supply. Check power supply
9 Dsp Error Return to Factory
10 Internal Command Parse Error (for use
during development, internal use only)
Return to Factory
11 AD Error AD sampling error, Return to Factory
12 Calibration Flash Error RF Calibration Flash Error, Return to Factory
13 Dsp Authentication Return to Factory
14 No Signal Error No signal back, will see no reflective echo on
echo curve
Check antenna aiming
Check if the application is having excessive
vapor/steam