December 2015 Quick Start Installation Guide 9
Table 2 - Conduit Adapters
Step
Action
1
Remove the protective plastic cap from the threaded conduit
entry.
2
To ensure the environmental ingress rating on tapered
threads (NPT), a non-hardening thread sealant may be used.
3
Thread the appropriate size adapter (½ NPT) into the conduit
entry opening
4
Tighten adapters according to the following table.
Description
Tool
Torque
½ to ¾ NPT Adapter
1 ¼” Wrench
32 Nm
24 Lb-ft
Figure 6: Electronic Housing Conduit Entries
Note. No conduit connectors or plugs come installed in the housings. All
housings come with temporary plastic dust protectors (red) installed and
are not certified for use in any installation