Installation Guide SMX-AUS
10 NS-MN-0030 / 11.2020
Table: Main PCB Interfaces
Designator Connection Wire Connections Power limited Designator Connection Wire Connections Power limited
J1 USB1 --- --- P11 Program Relay
Pin1 = NC
Pin2 = NO
Pin3 = COM
No
J2
USB2
Do not use
---
P12
AUX2
Do not use
---
J3
TCP/IP
Do not use
---
P13
Int Repeater
Do not use
---
J4 LCD Interface --- --- P15 DC Input (from PSU)
Pin1 = Input +
Pin2 = Input -
Yes
J5 CTP --- --- P16
Add-On Card
Interface
Do not use ---
J6
Add-on Card
Interface - AUX3
Power Card
via AUX Power Card Yes, through AUX Card P17 System-IO Do not use ---
P1 AUX1
Pin1 = Output +
Pin2 = Output -
Yes P18 Battery Input
Pin1 = Input +
Pin2 = Input -
No
P2 Ext Repeater
Pin1 = Out-A
Pin2 = Out-B
Pin3 = In-A (Do not use)
Pin4 = In-B (Do not use)
Yes P19 Printer
Pin1 = GND
Pin2 = TXD (Panel ->
Printer)
Pin4 = RXD (Printer ->
Panel)
Yes
P3 NAC1
Pin1 = Output +
Pin2 = Output -
Yes P20 Thermistor --- Yes
P4 NAC2
Pin1 = Output +
Pin2 = Output -
Yes P21 Network Do not use ---
P5 Loop1
Pin1 = Out+
Pin2 = Out-
Pin3 = In+
Pin4 = In-
Yes P22
Add-On Card
Interface
Do not use ---
P6 Loop2
Pin1 = Out+
Pin2 = Out-
Pin3 = In+
Pin4 = In-
Yes P23 Tamper Do not use ---
P7 Loop3 Do not use --- P24 Digital Input1
Pin1 = Input +
Pin2 = Input -
Yes
P8
Loop4
Do not use
---
P25
AUX Input
Do not use
---
P9 Alarm Relay
Pin1 = NC
Pin2 = NO
Pin3 = COM
No P26 Digital Input2
Pin1 = Input +
Pin2 = Input -
Yes
P10 Fault Relay
Pin1 = NC
Pin2 = NO
Pin3 = COM
No P27 MCP Selection
Cap On: For MCP2A
Cap Off: For Digital Input
Yes