Installation Guide SMX-AUS
NS-MN-0030 / 11.2020 25
4.2 Battery Calculations for 2-loops
Below table provides a sample sheet for calculating the battery values for 2-loops.
You are fully responsible for verifying these calculations.
Use the dropdowns and the yellow cells to enter values.
Table: Pluto AUS - battery Calcs_V9_Exercises_working
Standby Current (amps)
Secondary Alarm Current (amps)
Device Type
Qty
Current Draw
Total
Qty
Current Draw
Total
Main Circuit Board
1
x
0,260000
=
0,26000
1
x
0,330000
=
0,33000
ANN-BUS Devices
ANN-80(-W)
1
x
0,015000
=
0,015000
1
x
0,040000
=
0,040000
ANN-I/O
0
x
0,035000
=
0
x
0,200000
=
Addressable Devices
M500DMR
0
x
0,001300
=
M500DM
0
x
0,000750
=
M502M
0
x
0,000300
=
M500M
0
x
0,000400
=
M500R
0
x
0,000300
=
M501M
0
x
0,000400
=
M500S
198
x
0,000400
=
0,079200
M500X
0
x
0,000450
=
M512ME
0
x
0,000300
M900X
0
x
0,000350
=
M200XE
0
x
0,000200
=
M201E
0
x
0,000275
=
M201E-240
0
x
0,000275
=
M201E-240-DIN
0
x
0,000275
=
M210E-CZ
0
x
0,000288
=
M210E
0
x
0,000310
=
M220E
0
x
0,000340
=
M221E
0
x
0,000340
=
SC-6
0
x
0,002250
=
CZ-6
0
x
0,002000
=
CR-6
0
x
0,001450
=
IM-10
0
x
0,003500
=
2251BAUS
198
x
0,000300
=
0,059400
2251TLE
0
x
0,000200
=
2251TMBAUS
0
x
0,000300
=
2251CTLE
0
x
0,000200
=
5251RAUS
0
x
Not found
=
5251HAUS
0
x
Not found
=
5251BAUS
0
x
Not found
=
5251B-WP
0
x
Not found
=