What to do if Honeywell SILENT KNIGHT 6700 Control Panel doesn't recognize physically connected 5496 module?
- CChristian JohnsonAug 7, 2025
If a 5496 module physically connected to the Honeywell Control Panel isn't recognized, begin by checking the status of the 5496 green LED. If it flashes in a 0.5 sec on / 0.5 sec off pattern, the module likely hasn't been added to the system through programming. JumpStart can add connected 5496 modules, or you can add them manually. Ensure the correct ID for the 5496 module has been set via the DIP switches (ID#1 for the first, ID#2 for the second). If the LED isn't flashing, the wiring between the 5496 and the panel is likely incorrect. Also, measure the voltage from 5496 Terminal (+) to Terminal (-); it should be in the 27.2-27.4V range when AC power is present.