56 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Common Communication Link Setting the ID for Each Panel
Fiber-Optic and Twisted Pair Wiring between Multiple Panels
A mixture of fiber-optic cable and twisted-pair wiring between multiple panels is shown in Figure 5.9. Class X cabling is shown with a dot-
ted line.
5.5 Setting the ID for Each Panel
Use the DIP switch positions 1 through 5 to set the ID for each panel. Note that switches 7 and 8 are not used and should remain in the OFF
position. See the figure below for possible DIP switch settings. Address 0 is an invalid address and cannot be used.
port 1
Class X
wiring
port 2
last control panel/SK-NIC
next control panel/SK-NIC
first control panel/SK-NIC
port 1
port 2
port 1
port 2
in
out
in
out
in
out
in
out
Figure 5.9 Twisted-Pair and Fiber-Optic Combination Wiring Example
NOTE: It is important that much thought is given when choosing the IDs for each panel. It is difficult to change the IDs once panel
programming has begun.
17845623
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
17845623
Figure 5.10 Panel ID Settings
ON
OFF
Address Address Address Address