92 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
System Operation Basic Operation
Invalid Password/Panel Timeout
If a password is entered incorrectly or is not a valid password, the panel will display an error message. You must hit ENTER or the left arrow
key and re-enter the password correctly. After ten invalid attempts, the panel will panel will lock for 30 seconds and then you can try again.
However, if the password has been forgotten, record the 20-character code displayed on the panel and contact Technical Services. After
proper authentication, the password will be supplied.
9.2.2 Main Menu Overview
Table 9.2 lists a brief overview of the main menu after you have logged in to the panel. These options are described in greater detail through-
out this section of the manual.
9.2.3 Using the Menus
9.3 Basic Operation
9.3.1 Setting Time and Date
1. From the main menu, select 4 to access the Set Date and Time menu.
2. Make changes in the fields on the screen. Use the right arrow key to move through the fields. Use the up or down arrow key to make
selections.
3. When the date and time are correct, press ENTER.
9.3.2 Disable / Enable a Point
1. From the main menu, select 2 for Point Functions.
2. Select 1 for Disable/Enable Point.
Disable / Enable NACs by Template
1. Press 1 to Disable NACs by Template or press 2 to Enable NACs by Template.
2. Use the up or down arrow key to move through the list of templates. Press ENTER to select the current template.
Disable / Enable NACs by Group
1. Press 3 to Disable NACs by group or press 4 to Enable NACs by group.
2. Use the up or down arrow key to move through the list of groups. Press ENTER to select the highlighted group.
Disable / Enable Zone Points
1. Press 5 to Disable Zone Points or press 6 to Enable Zone Points.
2. Use the up or down arrow key to move through the list of zones. Press ENTER to select the highlighted zone.
Disable / Enable Point
1. Press 7 to Disable/Enable Point.
2. Select the module.
3. Use the up or down arrow key to choose the point and press ENTER.
4. Press the right arrow to disable or enable the point.
Main Menu Options Description
1- System Tests Access to Fire Drill, Indicator Test, Walk Tests, Communicator Test, Clear History Buffer, Manual AlarmNet
Registration, and Manual Communicator Reset.
2- Point Functions From here you can enable / disable points.
3- Event History Display event history on the LCD. See Section 9.3.4 for more information.
4- Set Time and Date Set time and date for the system.
5- Network Diagnostics Ping Panel and Data Network Status
6- Network Programming Access Learn Network, Edit Network Names, Edit Panel ID, Computer Access, Communicator Options, and
Sync Network Options.
7- Panel Programming Brings up a set of menus for programming the panel. These options are described in detail in Section 8.
8- System Information Menus to view information about the panel such as model, ID, serial number, revision, send or receive
firmware updates, and feature registration activation.
Table 9.2 Main Menu Options
To move through the menus: Use up and down arrows to move through the options in a Menu. Use the left arrow key to move to a previous menu.
To select an option: Enter the number of the option, OR press ENTER if the option appears at the top of the Menu (= symbol displays after
the option number in this case).
Table 9.3 Using the Menus