14 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Agency Listings, Approvals, and Requirements Underwriters Laboratories (UL)
2.2.6 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 72
When using carbon monoxide detection the system must be monitored by a Supervising Station with emergency response, both aspects meet-
ing the Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 72.
2.2.7 NFPA Requirements
The following is the minimum configuration necessary to comply with the NFPA requirements.
Model/Module Description Local Releasing
Remote
Station
Auxiliary
C e n t ra l
Station
Emergency
Signaling
067000 Control Unit Y Y Y Y Y Y
5220 Direct Connect Module N N N Y N O
5496 NAC Expander O Y* O O O O
5865-3/-4 LED Annunciator O O O O O O
5880 LED I/O Module O O O O O O
5895XL Intelligent Power Module O Y* O O O O
5860 LCD Annunciator O O O O O O
6860 LCD Annunciator O O O O O O
SK-NIC Network card O O O O O O
SK-FML/ -FSL Fiber modules O O O O O O
006700CB Enclosure Y Y Y Y Y Y
HWF2A-COM Communicator N N Y N Y N
HWF2V-COM Communicator N N Y N Y N
Y = YES, N = NO, O = OPTIONAL
Note: Y * = You must include the 5895XL or 5496 for releasing purposes.
Table 2.1 NFPA Requirement for Minimum System Configuration for 6700