SPM Flex Gas Detector
Introduction
The SPM Flex gas detector is an extractive gas monitoring system that draws 
gas samples locally or from a remote point to a Chemcassette
®
 tape-based 
optical gas detection system� A wide range of toxic gas Chemcassette cartridges 
are available that enable detection of gases used or generated in semiconductor 
manufacturing and industrial environments�  
The SPM Flex gas detector, available in wall mounted and portable versions, 
locally displays gas concentration, alarm, fault and status information via its 
backlit color LCD and LEDs� A simple to use 4-button keypad adjacent to the 
display provides the ability to set-up, review, operate and make changes to the 
detector’s configuration� The intuitive display and menu structure are designed 
to require minimal training� The SPM Flex has a local audio alarm with user-
configurable output levels� The detector can be used both indoors and outdoors 
in a wide range of weather conditions�
The detector has flexible power and communications capabilities� These include 
3 on-board relays, 4-20 mA analog output and Modbus/TCP outputs for signal 
and service connectivity� The gas detector is equipped with a USB port for 
configuration-sharing firmware updates and data downloads� For web-enabled 
devices, web pages are available via the Ethernet port�
Standard operation conditions 
The SPM Flex gas detector is designed for use in temperatures between 
32ºF and 104ºF (0ºC and 40ºC) and relative humidities between 0 and 100% 
(the relative humidities are limited by tape and calibration)� The sample line 
will require additional hardware to remove moisture in high relative humidity 
conditions where condensing may occur (the sample must be non-condensing)� 
Dry conditions may require humidification�
High-altitude applications 
The SPM Flex pump is optimized for operation at altitudes between –1000 feet 
(–305 meters) and 3000 ft� (945 m) above sea level� At altitudes above 3,000 ft� 
(915 m), up to a maximum of 6,000 ft� (1,830 m), contact Honeywell Analytics 
for  calibration�  (At 6,000 feet, pump capacity is reduced 18% and a flow-
system adjustment to the bypass valve is required� This must be performed by a 
Honeywell Analytics certified technician� Contact Customer Service�)