To verify fire
Delay
A2
Veri fy
Verification
If delay mode is ON, that is if the Delay light is
lit, the alarm sounders are inactive for a 30
seconds (factory set) duration. During this
time the alarm delay can be extended by a
pre-configured time (up to 10 minutes
maximum) by operating the Verify button.
Enter access level 2.
Press the Verify button.
The verification light is lit to show the fire
alarm delay has been extended.
NOTE: Operating Sound Alarms button or
if there is a subsequent fire event the
alarms are activated immediately.
To cancel buzzer
Cancel Buzzer
To silence the panel buzzer while the
system is in fire condition:
Press the Cancel Buzzer button.
To silence alarms
A2
Silence Alarms
To stop the fire alarm sounders from
sounding, for example once the building has
been evacuated and the fire fighters are
present to attend to the fire.
Enter access level 2.
Press the Silence Alarms button.
To reset the system
A2
Reset
After the emergency is over and the affected
devices have been restored for normal
operation and alarms have been silenced:
Enter access level 2
Press the Reset button.